FAQ-193: ICDA procedures in absence of NACE standard

Go To FAQ#:

Question: Currently, no standard exists for ICDA. How can we include ICDA in our plan when there is no accepted standard?

Answer: NACE is developing a standard for internal corrosion direct assessment (ICDA). OPS will consider incorporating that standard into the rule once it is approved. In the meantime, the rule, itself, includes requirements for ICDA that are consistent with drafts of the standard under development. Operators must follow the requirements in the rule and in ASME/ANSI B31.8S, Section 6.4 and Appendix B2 (referenced in the rule). Operators also must use the model in GRI 02-0057, "Internal Corrosion Direct Assessment of Gas Transmission Pipelines – Methodology" to identify ICDA regions (see 192.927(c)(2)). Operators must develop their own procedures based on the requirements in the rule and the referenced standard, and can also use the draft NACE standard as guidance.

These Frequently Asked Questions (FAQs) are intended to clarify, explain, and promote better understanding of the pipeline integrity management rules. These FAQs are not substantive rules and do not create rights, assign duties, or impose new obligations not outlined in the existing integrity management regulations and standards. Requests for informal interpretations regarding the applicability of one or more of the pipeline integrity management rules to a specific situation may be submitted to PHMSA in accordance with 49 C.F.R. § 190.11.